Specifications
Supply voltage230 V
Supply frequency50/60 Hz
Supply current (max)65 to 170 mA
Power factor0.96
Total circuit power (max)
Total circuit power (nominal)
Ambient temperature (ta)0 to +50°C
Max case temperature (tc)+75°C
Conductor size0.5 - 1.5mm²
Battery charge current (3 hour variant)190 mA
Battery charge current (1 hour variant)80 mA
Battery discharge current (nominal)1.05 A
Battery charge voltage4.8 to 6.0 V
Battery discharge voltage3.2 to 6.0 V
Emergency duration1 or 3 hours
Recharge period24 hours
Weight of control gear195 g
Features
Test Switch
Connecting a momentary push-to-make test switch (minimum rating of 10V, 30mA DC) to the ‘Test Switch’ terminals will allow the emergency operation of the module to be tested.
Voltage Sensing Circuit
The AC power supply is sensed so that switching occurs at between 60% and 85% of the nominal mains supply.
Indicator
The LED indicator is illuminated when a charge is flowing to the cells. Flexible 1x0.6mm high temperature orange and pink leads connect the indicator to the module. The indicator requires a 8mm hole.
Deep Discharge Protection
The inverter module incorporates deep discharge protection (DDP), to prevent damage to the batteries caused by deep discharge and possible subsequent reverse cell polarity.
Technology Options
Standard
For applications where self-testing is not required or suitable, the non-AutoTest® option provides the same quality and performance expected of Mackwell products, without the AutoTest® feature.
Relevant Standards
- EN 61347-1
- EN 61347-2-3
- EN 61347-2-7
- EN 60598-2-22
- BS 5266-1
- EN 62034
- EN 62386
- ICEL 1004
Notes
For Health & Safety reasons, removal or replacement of the lamps when the module is in operation is not recommended, but will have no adverse effects. The replacement lamp will immediately operate without the ballast having to be reset.