Specifications
Supply voltage230 V
Supply frequency50/60 Hz
Supply current (max)80 mA
Power factor0.4
Ambient temperature (ta)0 to +50°C
Max case temperature (tc)70°C
Conductor size0.5 - 1.5mm²
Battery charge current (3h - duration link in)200 mA
Battery charge current (1h - duration link out)90 mA
Battery discharge current (nominal)1.05 A
Battery charge voltage4.8 to 6.0 V
Battery discharge voltage3.5 to 5.6 W
Emergency duration1 or 3 hours
Recharge period24 hours
Weight of control gear130 g
Features
Switch Mode Power Supply
Mackwell patented Switch Mode Power Supply provides total short circuit protection, regulated output and complies with all relevant standards.
Ballast Delay Relay
All versions are fitted with an additional relay to switch off the power to the HF ballast during emergency lighting test.
Voltage Sensing Circuit
The AC power supply is sensed so that switching occurs at between 60% and 85% of the nominal mains supply.
Indicator
The LED indicator is illuminated when a charge is flowing to the cells. Flexible 1x0.6mm high temperature orange and pink leads connect the indicator to the module. The indicator requires a 8mm hole.
Deep Discharge Protection
The inverter module incorporates deep discharge protection (DDP), to prevent damage to the batteries caused by deep discharge and possible subsequent reverse cell polarity.
Technology Options
DALI AutoTest®
Provides benefits by enabling testing and monitoring of an emergency lighting system either on-site or via an internet connection. DALI AutoTest® is ideal for monitoring larger buildings and multiple sites. The product defaults to standalone AutoTest when not connected to a DALI network.
Relevant Standards
- EN 61347-1
- EN 61347-2-3
- EN 61347-2-7
- EN 60598-2-22
- BS 5266-1
- EN 62034
- EN 62386
- ICEL 1004
Notes
Caution
Charge batteries for 24 hours before commissioning. Do not insulation test this product. Reversing battery polarity will cause damage.