Specifications
Supply voltage230 V
Supply frequency50/60 Hz
Supply current (max)60 mA
Power factor0.4
Ambient temperature (ta)0 to +50°C
Max case temperature (tc)70°C
Conductor size0.5 - 1.5mm²
Battery charge current (3 hour variant)225 mA
Battery discharge current (nominal)1.05 A
Battery charge voltage7.2 to 9.0 V
Battery discharge voltage5.7 to 9.0 V
Emergency duration3 hours
Recharge period24 hours
Weight of control gear142 g
Features
SmartCharge™
SmartCharge™ applies an intermittent charging duty cycle designed for use with NiMH batteries. This provides energy efficient charging maintenance, reduced operating temperatures and optimum service life of NiMH batteries.
Switch Mode Power Supply
Mackwell patented Switch Mode Power Supply provides total short circuit protection, regulated output and complies with all relevant standards.
Ballast Delay Relay
All versions are fitted with an additional relay to switch off the power to the HF ballast during emergency lighting test.
Indicator
The LED indicator is illuminated when a charge is flowing to the cells. Flexible 1x0.6mm high temperature orange and pink leads connect the indicator to the module. The indicator requires a 8mm hole.
Lamp Optimisation Link
The selection of the link alters the circuitry within the module thus enabling the module to run the widest range of lamps often with increased lamp performance.
Deep Discharge Protection
The inverter module incorporates deep discharge protection (DDP), to prevent damage to the batteries caused by deep discharge and possible subsequent reverse cell polarity.
Technology Options
DALI AutoTest®
Provides benefits by enabling testing and monitoring of an emergency lighting system either on-site or via an internet connection. DALI AutoTest® is ideal for monitoring larger buildings and multiple sites. The product defaults to standalone AutoTest when not connected to a DALI network.
Relevant Standards
- EN 61347-1
- EN 61347-2-3
- EN 61347-2-7
- EN 60598-2-22
- BS 5266-1
- EN 62034
- EN 62386
- ICEL 1004
Notes
Caution
Limit high voltage wire length to 500mm maximum. Performance testing must be carried out and approved by user. Not suitable for Amalgam lamps. Charge batteries for 24 hours before commissioning. Do not insulation test this product. Reversing battery polarity will cause damage.